Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/10/2008 | ELECTRIC - TEMPORARY SERVICE | Approved | IVRS - Inspection :* | |
| 04/09/2008 | ELECTRIC - TEMPORARY SERVICE | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED PER CARL OF SOS |
|
| 04/04/2008 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO WIRE NUT AND TAPE UNUSED NEUTRALS AND HOTS IN PANEL-NOT PROTECTED ENOUGH RIGHT NOW 2) NEED TO ADD A BREAKER OR A KNOCKOUT PLUG ON DEAD FACE COVER 3) NEED TWO GROUND RODS 6' APART OR VERIFICATION OF EXISTING GROUND ROD 4) NO PERMIT ON SITE |