Permit: T08CM00007

Parcel: 116121950


Addresses:

1334 W ONTARIO ST

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Date Description Inspector Results Comments
04/10/2008 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection :*
04/09/2008 ELECTRIC - TEMPORARY SERVICE Not ready for Inspection IVRS - Inspection :*
1) CANCELLED PER CARL OF SOS
04/04/2008 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED TO WIRE NUT AND TAPE UNUSED NEUTRALS AND HOTS IN PANEL-NOT PROTECTED ENOUGH RIGHT NOW
2) NEED TO ADD A BREAKER OR A KNOCKOUT PLUG ON DEAD FACE COVER
3) NEED TWO GROUND RODS 6' APART OR VERIFICATION OF EXISTING GROUND ROD
4) NO PERMIT ON SITE