Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/27/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 05/22/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEAL DUCT JOINTS ON EXTERIOR INCLUDING SCREWS AND WELD PIN 2) PROVIDE FILTER ON OUTSIDE AIR 3) LOW VOLTAGE WIRING NEEDS TO BE IN CONDUIT 4) LINE VOLTAGE CONDUIT IS TO BE STRAPPED UP OFF GROUND 5) PROVIDE APPROVED CONNECTORS ON SEAL TITE AT UNIT 6) CONDENSATE NOT PROPERLY TERMINATED 7) SEAL FLASHING AT LINE SET PENETRATIONS 8) PROVIDE FILTER GRILL AND SUPPLY GRILL |