Inspection History: ELECTRIC - FINAL

Permit Number - T08CM00003

Inspection Description - ELECTRIC - FINAL

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
05/07/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
05/07/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/04/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL BONDING BUSHINGS AROUND CONCENTRICS AC DISCONNECTS HAVE 277V/480V CIRCUIT
2. ROOFTOP RECEPTACLES HAVE NO POWER
3. EMERGENCY CIRCUITS AND NORMAL CIRCUITS CANNOT SHARE SAME RACEWAY
4. EMERGENCY CIRCUITS TO BE IDENTIFIED @ JUNCTION BOXES