Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/07/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 05/07/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/04/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL BONDING BUSHINGS AROUND CONCENTRICS AC DISCONNECTS HAVE 277V/480V CIRCUIT 2. ROOFTOP RECEPTACLES HAVE NO POWER 3. EMERGENCY CIRCUITS AND NORMAL CIRCUITS CANNOT SHARE SAME RACEWAY 4. EMERGENCY CIRCUITS TO BE IDENTIFIED @ JUNCTION BOXES |