Inspection History: ELECTRIC - TEMP POWER FOR TEST

Permit Number - T08CM00002

Inspection Description - ELECTRIC - TEMP POWER FOR TEST

Inspection Status - Approved

Date Description Inspector Results Comments
11/20/2008 ELECTRIC - TEMP POWER FOR TEST Approved IVRS - Inspection :*
11/04/2008 ELECTRIC - TEMP POWER FOR TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BRACE SUPPLY CONDUCTORS AS PER MANUF. INSTRUCTIONS
2. PROVIDE BUSHINGS ON CONDUIT ENTRIES INTO SES
PER 326 NEC
3. SUPPORT 3/0 BARE G.E.C BELOW BUSS
4. #6 CONDUCTORS UNDER SIZED FOR PANEL HP11 - 100 AMP
OVERCURRENT PROVIDED. SHOULD BE #2 CU
11/03/2008 ELECTRIC - TEMP POWER FOR TEST Not ready for Inspection IVRS - Inspection :*
PLEASE HAVE ELEC. CONTR. ON SITE NEXT INSP.
10/29/2008 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection :*