Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
Permit Number - T08CM00002
Inspection Description - ELECTRIC - TEMP POWER FOR TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/20/2008 | ELECTRIC - TEMP POWER FOR TEST | Approved | IVRS - Inspection :* | |
11/04/2008 | ELECTRIC - TEMP POWER FOR TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BRACE SUPPLY CONDUCTORS AS PER MANUF. INSTRUCTIONS 2. PROVIDE BUSHINGS ON CONDUIT ENTRIES INTO SES PER 326 NEC 3. SUPPORT 3/0 BARE G.E.C BELOW BUSS 4. #6 CONDUCTORS UNDER SIZED FOR PANEL HP11 - 100 AMP OVERCURRENT PROVIDED. SHOULD BE #2 CU |
|
11/03/2008 | ELECTRIC - TEMP POWER FOR TEST | Not ready for Inspection | IVRS - Inspection :* PLEASE HAVE ELEC. CONTR. ON SITE NEXT INSP. |
|
10/29/2008 | ELECTRIC - TEMP POWER FOR TEST | Partial Approval | IVRS - Inspection :* |