Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA PLUMBING
Permit Number - T08BU02121
Inspection Description - POOL/SPA PLUMBING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/19/2009 | POOL/SPA PLUMBING | Approved | ||
08/18/2009 | POOL/SPA PLUMBING | Partial Approval | IVRS - Inspection :* 1) POTABLE WATER PIPING OK 2) PRESSURE RELIEF OK 3) REMOVE TAPE, PROVIDE FASTENERS FOR HEATER VENT CONNECTORS 4) DBL WALL TO HAVE MINIMUM 1" CLEARANCE FROM COMBUSTIBLES 5) VENTING TO RISE PROPERLY 6) SEE NOTE #2 FROM 7/29/09 |
|
07/29/2009 | POOL/SPA PLUMBING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) POTABLE WATER PIPING BELOW BACKFLOW DEVICE TO BE OF APPROVED MATERIAL FOR INTERIOR BLDG USE 2) WILL NEED MINIMUM RUN TEST ON SYSTEM FOR CONNECTION TO EXISTING PIPING TO BE EXPOSED OR PRESSURE TEST WITH WATER 3) PROVIDE VENTING SYSTEM FOR POOL HEATER PER PAGE #9 INSTALLATION INSTRUCTIONS 4) PRESSURE RELIEF SHALL HAVE APPROVED DRAINAGE PIPING GRAVITY DRAIN TO APPROVED RECEPTOR OR DAY LIGHT |
|
03/18/2009 | POOL/SPA PLUMBING | Partial Approval | IVRS - Inspection :* WATER TEST THRU POOL TO SOUTH/WEST CORNER DOCK OF BLD. OK 1. RECALL FOR CONTINUATION INTO EQUIPMENT ROOM (POOL HAS SEPARATE FILL AND HOSE BIB PIPING) |