Inspection History: FIRE - KITCHEN EXH HOOD FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/06/2009 | FIRE - KITCHEN EXH HOOD FINAL | Approved | ||
| 02/04/2009 | FIRE - KITCHEN EXH HOOD FINAL | Denied | 1.) Relocate the manual pull station to a location 10 ft. minimum, away from hazard. 2.) Relocate the nozzles for the : a.) Griddle b.) Salamander |
|
| 12/18/2008 | FIRE - KITCHEN EXH HOOD FINAL | Denied | EXHAUST FAN SHUT OFF. NOZZLE IMPROPERLY INSTALLED FOR SALMANDER. NEED TWO MORE LINKS. |