Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/01/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 05/01/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/28/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* COMPLETE ITEM #3 FROM INSPECTION ON 4/16/09 EMERGENCY SHUT-OFF CONTACTOR TO OPEN ALL CONDUCTORS TO PUMPS BOTH HOT AND NEUTRAL |
|
| 04/27/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. COMPLETE ITEMS #3 & #4 2. RECALL WHEN READY |
|
| 04/24/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 04/16/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. OPEN SEAL OFF's FOR INSPECTION PACKING NEVER INSPECTED 2. BREAKERS FOR PUMPS TO MEET REQUIREMENT OF NEC 514.11 3. EMERGENCY SHUT OFF FOR PUMPS TO MEET REQUIREMENTS OF NEC 514.11 4. GROUNDING TO MEET REQUIREMENTS OF NEC 514.16 AND 501.30 5. NEED TO PROVIDE MEANS OF SERVICING PER NEC 514.13 6. CONTRACTOR TO BE LISTED 7. HOW IS EMERGENCY CONTROL RESET? |