Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/25/2008 |
FIRE SPKLR - FINAL |
|
Approved |
|
| 11/18/2008 |
FIRE SPKLR - FINAL |
|
Denied |
CORRECT UPRIGHT COVERAGE OVER RISER ROOM. PLUG HEADS NOT NEEDED UNDER DUCT. ADD ONE UPRIGHT HEAD UNDER DUCT OVER 4' IN WIDTH. SUBMIT AN AS-BUILT PLAN WITH ACCURATE INFORMATION. AFTER THE CEILING TILE IS ADDED IN THE RISER ROOM, ADD ONE HEAD. ADD HEAD ABOVE STAIRS GOING TO I.T. ROOM & PLUG 2 HEADS IN I.T. ROOM. |