Permit: T08BU01985

Parcel: 140420950

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T08BU01985

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/25/2008 FIRE SPKLR - FINAL Approved
11/18/2008 FIRE SPKLR - FINAL Denied CORRECT UPRIGHT COVERAGE OVER RISER ROOM. PLUG HEADS NOT NEEDED UNDER DUCT. ADD ONE UPRIGHT HEAD UNDER DUCT OVER 4' IN WIDTH. SUBMIT AN AS-BUILT PLAN WITH ACCURATE INFORMATION. AFTER THE CEILING TILE IS ADDED IN THE RISER ROOM, ADD ONE HEAD. ADD HEAD ABOVE STAIRS GOING TO I.T. ROOM & PLUG 2 HEADS IN I.T. ROOM.