Inspection History Details
Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/12/2009 | EXCAVATION/LAYOUT REBAR & ZON | Approved | IVRS - Inspection :* AS PER PLANS -- OK TO POUR FOOTINGS |
|
| 01/09/2009 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : See detailed listing on site.| 999* OPTIONAL SPREAD FOOTING DETAIL #2; PAGE S1 CALLS FOR #6 REBAR 24" EACH WAY @ COLUMN; #5 REBAR WAS USED NOT PER PLAN |