Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/23/2012 | FIRE SPKLR - FINAL | Approved | Corrections done and flow test was completed. | |
| 08/20/2012 | FIRE SPKLR - FINAL | Denied | Correct sprinkler coverage by all duct work duct work over 48" wide all duct is 60" wide. Need sprinkler coverage under returns and exhaust vents all over 48" (52" X 52" square). |