Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T08BU01828
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/20/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1. CORRECTIONS NOTED BY M. RAMBER HAVE BEEN MADE 2. PRESSURE FIT TOP AT HORIZONTAL DUCT PART OF ORIGINAL LISTING DUCT FULLY COVERED WITH EXTINGUISHING SYSTEM. 3. DUCT THROUGH ATTIC & TO FAN 16GA. GALVANIZED 4. RETURN AIR OK; FAN OK WITHOUT HINGE KIT |
|
| 11/20/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE ACCESS TO ROOF |
|
| 10/24/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE GREASE TROUGH ON ROOF 2. PROVIDE HINGED BASE AT EXHAUST FAN TO ALLOW FOR GREASE DUCT CLEANING 3. UNABLE TO ACCESS ABOVE CEILING 4. HOOD SEAMS SPLIT NEED TO BE RE-WELDED 5. EXHAUST AND MAKE UP AIR NOT INTERLOCKED |
|
| 10/21/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ON SITE AT 3:09 NO ONE ON SITE |
|
| 10/20/2008 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* |