Permit: T08BU01777

Parcel: 11615190K

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T08BU01777

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/13/2009 FIRE - ALARM FINAL Approved
01/09/2009 FIRE - ALARM FINAL Denied Not Approved 1/09/09.
1.) Central alarm not receiving alarms accurately. Unable to identify water flow alarm or pull station alarms.
2.) Central alarm receiving from one phone line but unable to determin if it is from the primary or the secondary line or if the secondary line is even functioning.
01/06/2009 FIRE - ALARM FINAL Denied Need telephone lines hooked up X 2 or have this panel report to main panel.
Need flow switch hooked to panel or have this panel report to main panel.
Need lock out on breaker