Permit: T08BU01774

Parcel: 127070560


Addresses:

5112 E 8TH ST

Inspection Status: Denied

Inspection History: FIRE SPKLR - UG, PIPING, HYDRO

Date Description Inspector Results Comments
09/15/2010 FIRE SPKLR - UG, PIPING, HYDRO Denied WRONG SIZE UNDER GROUND PIPING INSTALLED 1 1/2 INCH PCV NEED 2 INCH PCV ACCORDING TO PLANS. WILL APPROVED IF NEW CALS WORK OUT. DID DO FLUSH IN CASE CALS WORK WE CAN JUST APPROVED BOTH TEST PSI AND FLUSH.
09/15/2010 FIRE SPKLR - UG, PIPING, HYDRO Approved