Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/23/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* HOOD/MUA INTERLOCK OK AWAITING RESULTS OF APPEAL ON WELDED DUCT |
|
| 10/15/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - EXHAUST DUCTS ON ROOF DO NOT MEET TYPE 1 REQUIREMENTS. - MUST USE 16 GA. WELDED DUCTS. - HOOD & EXHAUST FAN APPEAR TO BE TYPE 1 - MAKE UP AIR MUST BE INTERLOCKED WITH EXHAUST FAN |
|
| 09/17/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* THERE IS NO TYPE I EQUIPMENT AT THIS ADDRESS THIS IS THE WRONG ADDRESS FOR INSPECTION |