Permit: T08BU01666

Parcel: 129020870


Addresses:

2744 E BROADWAY BL

Inspection Status: Partial Approval

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/23/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
HOOD/MUA INTERLOCK OK
AWAITING RESULTS OF APPEAL ON WELDED DUCT
10/15/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- EXHAUST DUCTS ON ROOF DO NOT MEET TYPE 1 REQUIREMENTS.
- MUST USE 16 GA. WELDED DUCTS.
- HOOD & EXHAUST FAN APPEAR TO BE TYPE 1
- MAKE UP AIR MUST BE INTERLOCKED WITH EXHAUST FAN
09/17/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
THERE IS NO TYPE I EQUIPMENT AT THIS ADDRESS
THIS IS THE WRONG ADDRESS FOR INSPECTION