Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/08/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 08/01/2008 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. HOOD EXHAUST SYSTEM AND MAKE UP AIR MUST BE INTERLOCKED 2. EXHAUST FANS MUST HAVE HINGE KITS TO ALLOW ACCESS FOR DUCT CLEANING |
|
| 07/31/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. EXTEND GAS LINE, FLEX CANNOT EXCEED 3FOOT 2. COVER SHARP EDGES OF WALL FLASHING 3. PROVIDE LADDER TO COMPLETE INSPECTION ON ROOF |