Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/30/2008 |
FIRE SPKLR - FINAL |
|
Approved |
|
| 09/25/2008 |
FIRE SPKLR - FINAL |
|
Partial Approval |
CHANGE OUT SPR. CONTROL VALVE & DO ANNUAL SPR. INSP. |
| 09/08/2008 |
FIRE SPKLR - FINAL |
|
Denied |
1 UPRIGHT HEAD LEAKS BY DRAFT STOP. NEED AN ANNUAL SPR. INSP. REPORT. MONITOR SYSTEM. REPLACE FDC CAPS. REPAIR ANY DEFICIENIES THAT MAY APPEAR ON ANNUAL SPR. REPORT. |
| 09/04/2008 |
FIRE SPKLR - FINAL |
|
Denied |
RELOCATE UPRIGHTS @ DINING DRAFT STOP. RELOCATE 2 PENDANTS @ SOUTH DINING AREA TOO FAR OFF WALL. ADD 1 PENDANT @ DINING OUTSIDE BUMPER CARS. RELOCATE 1 UPRIGHT @ REDEMPTION AREA. ADD 1 PENDANT OUTSIDE OF KITCHEN @ DINING AREA. ADD 1 PENDANT @ KITCHEN HOOD. RELOCATE 1 UPRIGHT @ KITCHEN HALLWAY & REPLACE PAINTED SSU. TAPE ON SSU @ RISER ROOM. NEED ANNUAL SPR. INSPECTION REPORT, HEADBOX & FDC CAPS. RISER NEEDS TO BE MONITORED WITH FLOW & TAMPER. ADD SPRINKLER HEADS OUTSIDE OF MAIN ENTRANCE ON N.W. CORNER OF BUILDING & OUTSIDE S.W. EXIT DOOR. |