Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/26/2008 | FIRE - ALARM FINAL | Approved | ||
| 08/07/2008 | FIRE - ALARM FINAL | Partial Approval | Temp C of O only Repair horn strobe by kiln room Repair horn strobe by door 48 Change strobe to horn /strobe by janitors closet Library classroom, relocate on smoke Horns in classrooms by doors 120 thru 124 and exterior horn not working outside horn, southside, not working properly Signal circuit still needs to be tested |
|
| 08/01/2008 | FIRE - ALARM FINAL | Not ready for Inspection | Not Ready. 1.) Heat dtectors closer then 12 " from light fixture a.) janitors closet door #6 b.) library south E/W wall c.) kitchen, custodial and by hood area. d.) cafateria storage e.) basement under library f.) closet, principles office. 2.) add one smoke detector in libratry classroom. |
|
| 07/29/2008 | FIRE - ALARM FINAL | Not ready for Inspection |