Permit: T08BU01131

Parcel: 137293980


Addresses:

1891 W SAVOY PL

Inspection Status: Approved

Inspection History: POOL/SPA FINAL/BARRIER

Date Description Inspector Results Comments
08/29/2008 POOL/SPA FINAL/BARRIER Approved IVRS - Inspection :*
1) NO SVRS REQUIRED
2) INSURE CAP FROM VACUUM BREAKER LINE IS REMOVED
08/27/2008 POOL/SPA FINAL/BARRIER Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FENCE WITHIN 5' OF WATER MUST BE BONDED
2) LABEL BREAKERS IN POOL SUB PANEL
3) NO SVRS REQUIRED
08/26/2008 POOL/SPA FINAL/BARRIER Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LABEL ALL CIRCUITS IN POOL PANEL
2) BOND METAL FENCE TO MAIN POOL BOND GRID (NOT DECK BOND GRID)
3) USE BELL COVERS FOR RECEPTS. YOU MUST BE ABLE TO PLUG IN CORD AND CLOSE THE WEATHER PROOF COVER
4) WAS A & A DRAIN SYSTEM INSTALLED ? PLAN IS NOT STAMPED, NO 2" VACUUM VENT AT POOL DECK. INSTALL SVRS UNIT
5) NO MORE THAN 4" GAP AT BOTTOM OF FENCE
6) SUPPORT H20 LINE AT ANTI-SIPHON/VERTICAL
08/25/2008 POOL/SPA FINAL/BARRIER Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WHEN GATE IS RELEASED FROM 1' OPEN IT DOES NOT LATCH
08/19/2008 POOL/SPA FINAL/BARRIER Cancelled
08/19/2008 POOL/SPA FINAL/BARRIER Not ready for Inspection IVRS - Inspection :*
07/15/2008 POOL/SPA FINAL/BARRIER Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/11/2008 POOL/SPA FINAL/BARRIER Not ready for Inspection IVRS - Inspection :*