Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA PLUMBING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/25/2008 | POOL/SPA PLUMBING | Approved | IVRS - Inspection :* | |
| 07/18/2008 | POOL/SPA PLUMBING | Partial Approval | IVRS - Inspection :* 1) INSTALL VACUUM BREAKER ON HOSE BIB 2) BOND LIGHT JUNCTION BOX 3) UNABLE TO DETERMINE SUPPLY WIRE SIZE 4) 90 AMP BREAKER AT MAIN PANEL AND 70 AMP AT SUB-PANEL 5) RESOLVE WIRE SIZES BY LEAVING A PIECE WITH LEGIBLE MARKINGS ON SITE |
|
| 07/15/2008 | POOL/SPA PLUMBING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) POOL AREA FLOODED RECALL WHEN DRY |
|
| 07/11/2008 | POOL/SPA PLUMBING | Not ready for Inspection | IVRS - Inspection :* CANCELED PER BELINDA |