Permit: T08BU01130

Parcel: 125050050


Addresses:

2421 E 3RD ST

Inspection Status: Approved

Inspection History: POOL/SPA ELECTRIC

Date Description Inspector Results Comments
08/12/2008 POOL/SPA ELECTRIC Approved IVRS - Inspection :*
08/08/2008 POOL/SPA ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED GFCI PROTECTION ON FOR RECEPT. PORCH
2) LEAVE LISTING FOR COMPOUND USED ON BOND CONNECTION IN WET NICHE FIXTURE
3) LEAVE HEATER INSTALL INSTRUCTION, T & P VALVE NOT INSTALLED PER MANUFACTURER INSTRUCTION ON LABEL ATTACHED TO VALVE
4) TOOK ? MANUAL WITH ME I WILL RETURN IT, I NEED TO VERIFY IF IT IS APPROVED FOR USE BY THE CITY
5) BOND JUNCTION BOX, HOUSE WIRING TO POOL LIGHT
6) REAR GATE DOESN'T SELF CLOSE
07/23/2008 POOL/SPA ELECTRIC Not ready for Inspection IVRS - Inspection :*
07/09/2008 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*