Permit: T08BU01111

Parcel: 141175500

Inspection Status: Approved

Inspection History: POOL/SPA FINAL/BARRIER

Date Description Inspector Results Comments
09/09/2008 POOL/SPA FINAL/BARRIER Approved IVRS - Inspection :*
09/04/2008 POOL/SPA FINAL/BARRIER Partial Approval IVRS - Inspection :*
1) BOND LIGHT J-BOX, LUG CONNECTION AT BOTTOM OF BOX
2) INSTALL LIGHT AT POOL DECK OR REMOVE WIRE
3) SAME THING WITH SPA WIRING
4) INSIDE SERVICE PANEL SMOKE DETECTOR CIRCUIT IS DISCONNECTED
5) NEED BUSHING FOR SPA CIRCUIT, PASSES THRU METAL CABINET