Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T08BU01078
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/02/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 06/30/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* MAKE UP AIR NOT WORKING EXTEND EXHAUST FAN ABOVE TOP OF COOLER MIN. 2' |
|
| 06/26/2008 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* INTERLOCK = HOOD EXHAUST IS TO BE TIED INTO THE SAME SWITCH AS THE MAKE UP AIR (COOLER) TO THAT WHEN ONLY ONE SWITCH IS TURNED ON, BOTH MAKE UP AND EXHAUST OPERATE TOGETHER |
|
| 06/19/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* INTERLOCK FAN MOTOR FROM FURNACE WITH EXHAUST FAN ON ROOF. SEE SECTION 508.1 2006 IMC PROVIDE A GREASE CUP ON EXHAUST FAN DRAIN GREASE FITTERS MUST BE REMOVABLE |
|
| 06/17/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* DO NOT SCHEDULE INSPECTIONS UNLESS SOMEONE IS AVAILABLE AND ON SITE PROVIDE ACCESS TO ALL AREAS REQUIRED |