Permit: T08BU01012

Parcel: 141013190


Addresses:

5068 S CIVANO BL


Inspection Status: Approved

Inspection History: POOL/SPA ELECTRIC

Permit Number - T08BU01012

Inspection Description - POOL/SPA ELECTRIC

Inspection Status - Approved

Date Description Inspector Results Comments
07/02/2008 POOL/SPA ELECTRIC Approved IVRS - Inspection :*
06/24/2008 POOL/SPA ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) #6 AL GOOD FOR 40 AMPS ONLY ROMEX
2) ISOLATE NEUTRALS GRDS AT SUB POOL PANEL, USE NO LOX
06/10/2008 POOL/SPA ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PLAN CALLS FOR 60 AMP CIRCUIT AT POOL. WIRE IS N/M #6 AL=50 AMPS
2) SPA TO BE 5'-0"=60" FROM WINDOW UNLESS WINDOW IS SAFETY GLASS