Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA ELECTRIC
Permit Number - T08BU01012
Inspection Description - POOL/SPA ELECTRIC
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/02/2008 | POOL/SPA ELECTRIC | Approved | IVRS - Inspection :* | |
06/24/2008 | POOL/SPA ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) #6 AL GOOD FOR 40 AMPS ONLY ROMEX 2) ISOLATE NEUTRALS GRDS AT SUB POOL PANEL, USE NO LOX |
|