Permit: T08BU00990

Parcel: 14029003H

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T08BU00990

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/07/2009 FIRE SPKLR - FINAL Approved
10/13/2008 FIRE SPKLR - FINAL Partial Approval Temp C of O approved. Sprinkler heads shall be 1" below drop ceiling for proper operation, this will stop final C of O if all heads are not adjusted when final is called in.
10/07/2008 FIRE SPKLR - FINAL Not ready for Inspection Sprinkler heads are to far up into the drop ceiling sprinkler defectors shall be hanging down in the clear for proper operations. Shall check throughout the business.