Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA ELECTRIC
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2008 | POOL/SPA ELECTRIC | Approved | IVRS - Inspection :* | |
| 07/17/2008 | POOL/SPA ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PVC CONDUIT NEEDS TO BE BURIED MINIMUM 18" DEEP 2) BOND WIRE NOT CONNECTED TO REBAR CAGE 3) BONDING LOOP OR LEADS FOR BONDING LOOP NOT INSTALLED |