Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA ELECTRIC
Permit Number - T08BU00899
Inspection Description - POOL/SPA ELECTRIC
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/23/2008 | POOL/SPA ELECTRIC | Approved | IVRS - Inspection :* | |
06/17/2008 | POOL/SPA ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO ONE HOME 2) PLEASE RECALL INSPECTION |
|
06/11/2008 | POOL/SPA ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. (60 AMP.) BREAKER NEEDED AT SERVICE 2. STILL #8 WIRE AT DISCONNECT 3. SECURE DISCONNECT TO WALL |
|
05/28/2008 | POOL/SPA ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PREVIOUS INSPECTION NOT TAKEN CARE OF |
|
05/27/2008 | POOL/SPA ELECTRIC | Partial Approval | IVRS - Inspection :* 1) 60 AMP BREAKER NOT COMPATIBLE WITH #8 CU. WIRE #6 REQUIRED MIN |