Permit: T08BU00899

Parcel: 141305530

Inspection Status: Approved

Inspection History: POOL/SPA ELECTRIC

Permit Number - T08BU00899

Inspection Description - POOL/SPA ELECTRIC

Inspection Status - Approved

Date Description Inspector Results Comments
06/23/2008 POOL/SPA ELECTRIC Approved IVRS - Inspection :*
06/17/2008 POOL/SPA ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO ONE HOME
2) PLEASE RECALL INSPECTION
06/11/2008 POOL/SPA ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. (60 AMP.) BREAKER NEEDED AT SERVICE
2. STILL #8 WIRE AT DISCONNECT
3. SECURE DISCONNECT TO WALL
05/28/2008 POOL/SPA ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PREVIOUS INSPECTION NOT TAKEN CARE OF
05/27/2008 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
1) 60 AMP BREAKER NOT COMPATIBLE WITH #8 CU. WIRE #6 REQUIRED MIN