Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
Permit Number - T08BU00867
Inspection Description - FIRE SPKLR - OH PIPING & HYDRO
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/12/2009 | FIRE SPKLR - OH PIPING & HYDRO | Approved | ||
02/26/2009 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 225 PSI FOR 2 HRS ON SYSTEMS #11-10-9-8-7 FOR SPRINKLERS ADDED UNDER CONEYORS IN STORGE WAREHOUSE NEED CORRECT SPRINKLER COVERAGE 1ST FL MIDDLE SYSTEM. |
|
02/24/2009 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | SYSTEMS: #29-30-31-32 AND PUMP HOUSE 225 PSI FOR 2 HOURS QUICK PICK AREAS: 1.) CHECK SPRINKLER COVERAGE BY CONDUIT ON 2ND FLOOR 2.) CHECK SAPRINKLER COVERAGE BY TRASH CHUTES 1ST AND 2ND FLOOR 3.) REPLACE BENT SPRINKLER HEAD 2ND FLOOR 4.) NEED TO CHANGE PRESSURE RELIEF SET UP ON ALL RISERS. SYSTEM SET UP AS OF NOW WILL NOT WORK. |
|
02/10/2009 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 225 PSI FOR 2 HOURS RISERS 3-4-5-6 | |
02/09/2009 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 225 PSI TEST FOR 2 HOURS RISERS 1-2-15-16 | |
02/05/2009 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 225 PSI TEST FOR 2 HOURS RISERS 17-18-19-20 | |
01/26/2009 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 225 PSI TEST FOR 2 HOURS RISERS 7,8,9,10,11,12,13,14. | |
01/21/2009 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 225 PSI TEST FOR 2 HOURS RISERS 21, 22, 23, 24 AND DRY PIPING TO OUTSIDE PATIO,still need to do trip test on dry system. | |
01/20/2009 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 225 PSI TEST FOR 2HRS RISERS #25,26,27,28. | |
01/16/2009 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 225 PSI TEST FOR 2 HOURS RISER #33 | |
01/14/2009 | FIRE SPKLR - OH PIPING & HYDRO | Cancelled | DID SECOND FIRE PUMP TEST ON ENGINE BECAUSE OF BACK FLOW INSTALLED ON LINE. NEED PUMP TEST RESULTS | |
12/16/2008 | FIRE SPKLR - OH PIPING & HYDRO | Cancelled | ||
06/17/2008 | FIRE SPKLR - OH PIPING & HYDRO | Cancelled | TALKED TO SHAMBAUGH THEY CANCELLED INSPECTION |