Permit: T08BU00816

Parcel: 13615017B

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/02/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
CORRECTIONS HAVE BEEN MADE
05/30/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection
CORRECTIONS HAVE BEEN MADE
PROVIDE A CLEANOUT ON TOP OF GREASE DUCT ON ROOF
05/13/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- SOUTH HOOD & EXHAUST EQUIPMENT ARE OK
- NORTH HOOD & EXHAUST FAN ARE OK BUT THE DUCT ON THE ROOF CONNECTING TO THE FAN IS NOT TYPE 1 RATED.
- REPLACE DUCT WITH 16ga WELDED DUCT
- INTERLOCK MAKE UP AIR UNIT WITH EXHAUST FANS
- RECALL FOR INSPECTION
- OK TO INSTALL FIRE SUPPRESSION SYSTEM
- PROVIDE CORRECT ADDRESS ON PERMIT