Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/02/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
| 05/30/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection CORRECTIONS HAVE BEEN MADE PROVIDE A CLEANOUT ON TOP OF GREASE DUCT ON ROOF |
|
| 05/13/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - SOUTH HOOD & EXHAUST EQUIPMENT ARE OK - NORTH HOOD & EXHAUST FAN ARE OK BUT THE DUCT ON THE ROOF CONNECTING TO THE FAN IS NOT TYPE 1 RATED. - REPLACE DUCT WITH 16ga WELDED DUCT - INTERLOCK MAKE UP AIR UNIT WITH EXHAUST FANS - RECALL FOR INSPECTION - OK TO INSTALL FIRE SUPPRESSION SYSTEM - PROVIDE CORRECT ADDRESS ON PERMIT |