Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/22/2008 | FIRE - ALARM FINAL | Approved | ||
| 08/21/2008 | FIRE - ALARM FINAL | Denied | 1.) investigate problem with battery pack 2.) Provide "AS BUILT" plans. ( OK to APPROVE when battery problem is addressed) |
|
| 06/04/2008 | FIRE - ALARM FINAL | Denied | Not approved 6/4/08 Needs to connect transmitter to monitor. Ares tested and approved: 1.) Smoke detector location 2.) Strobes 3.) Alarms 4.) Water flow switch 5.) Sprinkler valve tamper switch 6.) Ground fault 7.) Tamper / trouble indications 8.) individule smoke test 9.) Class "A" loop fault 10.) NAC circuit |