Permit: T08BU00757

Parcel: 128140630


Addresses:

5232 E 18TH ST

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
08/22/2008 FIRE - ALARM FINAL Approved
08/21/2008 FIRE - ALARM FINAL Denied 1.) investigate problem with battery pack
2.) Provide "AS BUILT" plans. ( OK to APPROVE when battery problem is addressed)
06/04/2008 FIRE - ALARM FINAL Denied Not approved 6/4/08

Needs to connect transmitter to monitor.
Ares tested and approved:
1.) Smoke detector location
2.) Strobes
3.) Alarms
4.) Water flow switch
5.) Sprinkler valve tamper switch
6.) Ground fault
7.) Tamper / trouble indications
8.) individule smoke test
9.) Class "A" loop fault
10.) NAC circuit