Permit: T08BU00667

Parcel: 133170630


Addresses:

350 N WILMOT RD

Inspection Status: Approved

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Date Description Inspector Results Comments
10/23/2008 FIRE SPKLR - OH PIPING & HYDRO Approved
09/25/2008 FIRE SPKLR - OH PIPING & HYDRO Partial Approval Temp C of O approved for the following areas
a. South end of OR#3
b. South CT Equipment
c. South Sterile room
09/17/2008 FIRE SPKLR - OH PIPING & HYDRO Partial Approval Temp C of O approved for the following areas:
a. South end OR#3
b. South CT Equipment
c. South Sterile room
1. Need to correct sprinkler coverage in OR#1
2. Need to add sprinkler coverage in CT park area
When adding heads to sprinkler system do not use south CT rooms when system is down.
07/11/2008 FIRE SPKLR - OH PIPING & HYDRO Partial Approval Overhead PSI test approved
In all three equipment rooms ceiling drops going in?? If not them add uprights.
In CT Gantry room northwest corner sprinkler head obstructed by soffit.