Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/15/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. DUCT AT HOODS NOT PROPER GAUGE (16 MIN.) 2. HOLES IN HOOD NEED TO BE PATCHED 3. BREAKER AT SUB-PANEL NOT TO BE USED AS ON/OFF SWITCH FOR HOODS 4. HOODS AND MAKE UP AIR NOT INTERLOCKED 5. EXHAUST FANS MISSING MOTORS COMPLETELY DESTROYED OR OTHERWISE IN DISREPAIR 6. DUCT TO EXHAUST FANS ON ROOF NOT PROPER GAUGE AND NOT WELDED 7. MAKE UP AIR UNITS ON ROOF IN TOTAL DISREPAIR OR MISSING FROM ROOF ONLY 1 UNIT REMAINS |