Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA ELECTRIC
Permit Number - T08BU00437
Inspection Description - POOL/SPA ELECTRIC
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/11/2008 | POOL/SPA ELECTRIC | Approved | IVRS - Inspection :* | |
09/10/2008 | POOL/SPA ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* PERMIT/PLANS? MUST BE POSTED ON SITE |
|
07/10/2008 | POOL/SPA ELECTRIC | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. INSTALL EMERGENCY SHUT OFF SWITCH PROPERLY 2. PLEASE BREAK TABS SO AS GFCI COVER WILL OPEN 3. PROPERLY SUPPORT NM CABLE 4. NM SHEATHING TO ENTER BOX 1/4" 5. PROTECT NM CABLE FROM PHYSICAL DAMAGE 6. BREAKER AMPACITY TO MATCH NM CABLE 7. ELECTRICAL FOR PANES AND POOL ROOM NOT AS PER PLAN 8. NUMEROUS VIOLATIONS OBSERVED - HAVE QUALIFIED ELECTRICIAN REPAIR |
|
05/12/2008 | POOL/SPA ELECTRIC | Not ready for Inspection | IVRS - Inspection :* ELECTRICAL FINAL WILL NOT BE MADE BEFORE POOL IS COMPLETE, FULLY OPERATIONAL AND READY TO USE. OK INSULATED #8 CU AND COMPOUND TO LIGHT FIXTURE. |
|
04/28/2008 | POOL/SPA ELECTRIC | Partial Approval | IVRS - Inspection :* OK TO POUR DECK OK GRAB RAILS, HANDICAP ANCHOR ETC. |
|
04/21/2008 | POOL/SPA ELECTRIC | Partial Approval | IVRS - Inspection :* |