Permit: T08BU00437

Parcel: 124082110


Addresses:

55 N CHERRY AV


Inspection Status: Approved

Inspection History: POOL/SPA ELECTRIC

Permit Number - T08BU00437

Inspection Description - POOL/SPA ELECTRIC

Inspection Status - Approved

Date Description Inspector Results Comments
09/11/2008 POOL/SPA ELECTRIC Approved IVRS - Inspection :*
09/10/2008 POOL/SPA ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999*
PERMIT/PLANS?

MUST BE POSTED ON SITE
07/10/2008 POOL/SPA ELECTRIC Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. INSTALL EMERGENCY SHUT OFF SWITCH PROPERLY
2. PLEASE BREAK TABS SO AS GFCI COVER WILL OPEN
3. PROPERLY SUPPORT NM CABLE
4. NM SHEATHING TO ENTER BOX 1/4"
5. PROTECT NM CABLE FROM PHYSICAL DAMAGE
6. BREAKER AMPACITY TO MATCH NM CABLE
7. ELECTRICAL FOR PANES AND POOL ROOM NOT AS PER PLAN
8. NUMEROUS VIOLATIONS OBSERVED - HAVE QUALIFIED ELECTRICIAN REPAIR
05/12/2008 POOL/SPA ELECTRIC Not ready for Inspection IVRS - Inspection :*
ELECTRICAL FINAL WILL NOT BE MADE BEFORE POOL IS COMPLETE, FULLY OPERATIONAL AND READY TO USE.

OK INSULATED #8 CU AND COMPOUND TO LIGHT FIXTURE.
04/28/2008 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
OK TO POUR DECK
OK GRAB RAILS, HANDICAP ANCHOR ETC.
04/21/2008 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*