Permit: T08BU00413

Parcel: 141185530


Addresses:

9337 E OLD VAIL RD

Inspection Status: Approved

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Date Description Inspector Results Comments
07/08/2008 FIRE SPKLR - OH PIPING & HYDRO Approved As builts turned in with changes.
06/23/2008 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 200PSI for 2 hours approved
Need as built for changes around duck work, pipe size changes in office area.
Contractor asked if entrance canopy was built non-combustible do they still need to sprinkler. Canopy does not need to be sprinkled if it's non-combustible construction only. Need a letter stating that no combustibles will be stored under front canopy over entrance doors.
Need cals to show back flow prevention on line or remove back flow.