Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/08/2008 | FIRE SPKLR - OH PIPING & HYDRO | Approved | As builts turned in with changes. | |
| 06/23/2008 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 200PSI for 2 hours approved Need as built for changes around duck work, pipe size changes in office area. Contractor asked if entrance canopy was built non-combustible do they still need to sprinkler. Canopy does not need to be sprinkled if it's non-combustible construction only. Need a letter stating that no combustibles will be stored under front canopy over entrance doors. Need cals to show back flow prevention on line or remove back flow. |