Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T08BU00395
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/22/2008 | FIRE - ALARM FINAL | Approved | ||
03/03/2008 | FIRE - ALARM FINAL | Partial Approval | TEMP C OF O OK -- NEED FOLLOWING AREAS CORRECTED 1.) Corridor #122 north end of corridor move smoke detector, to close to A/C vent must be 3 feet a way from all intake and exhaust. 2.) Install smoke detector in room where fire alarm panel is located, this is for the protection of the panel. 3.) Corridor #140 move smoke detectors 3' a way from all A/C vents, must be 3 feet a way from all intake and exhaust. 4.) Rooms 219 and 220 move strobes and horn from behind doors, blocking strobe lights. |