Permit: T08BU00395

Parcel: 11011181B


Addresses:

5099 E GRANT RD

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
04/22/2008 FIRE - ALARM FINAL Approved
03/03/2008 FIRE - ALARM FINAL Partial Approval TEMP C OF O OK -- NEED FOLLOWING AREAS CORRECTED
1.) Corridor #122 north end of corridor move smoke detector, to close to A/C vent must be 3 feet a way from all intake and exhaust.
2.) Install smoke detector in room where fire alarm panel is located, this is for the protection of the panel.
3.) Corridor #140 move smoke detectors 3' a way from all A/C vents, must be 3 feet a way from all intake and exhaust.
4.) Rooms 219 and 220 move strobes and horn from behind doors, blocking strobe lights.