Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T08BU00393
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/08/2008 | FIRE - ALARM FINAL | Approved | ||
07/30/2008 | FIRE - ALARM FINAL | Partial Approval | 1. Relocate smoke detector in Lobby 210 (separation requirements) 2. Relocate heat detector in Janitor 201 - 12" from light 3. Provide current zone map to reflect new addition & devices 4. Add strobes in rooms 216 &219 5. LCD display |