Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA FINAL/BARRIER
Permit Number - T08BU00270
Inspection Description - POOL/SPA FINAL/BARRIER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/13/2008 | POOL/SPA FINAL/BARRIER | Approved | IVRS - Inspection :* 1) SVRS #027363 |
|
06/05/2008 | POOL/SPA FINAL/BARRIER | Denied | 1) BOND BARRIER EAST END WITHIN 5' WATERS EDGE 2) GATE AT N.W. CORNER DOES NOT SELF LATCH. 4" SPHERE GREATER AT BOTTOM OF GATE 3) POOL HOUSE GATE DOES NOT SELF LATCH |
|
06/03/2008 | POOL/SPA FINAL/BARRIER | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DOORS TO EQUIPMENT AREA AND MAIN ENTRANCE MUST BE SELF CLOSING AND SELF LATCHING 2) NEED TO BURY FLEX CONDUIT, CANNOT BE WALING ON TOP OF IT |
|
05/30/2008 | POOL/SPA FINAL/BARRIER | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MISSING VACUUM RELIEF SYSTEM PER ASME 112.19.17 2) ALL GATES AND DOORS MUST BE SELF LATCHING, SELF CLOSING AND OPEN AWAY FROM POOL |