Permit: T08BU00118

Parcel: 141353250


Addresses:

5970 S JAKEMP TR


Inspection Status: Approved

Inspection History: POOL/SPA PRE-GUNITE

Permit Number - T08BU00118

Inspection Description - POOL/SPA PRE-GUNITE

Inspection Status - Approved

Date Description Inspector Results Comments
04/07/2008 POOL/SPA PRE-GUNITE Approved
03/05/2008 POOL/SPA PRE-GUNITE Partial Approval IVRS - Inspection :*
1) PLEASE INSTALL #8 CU. AROUND POOL PERIMETER 18"-24" AWAY FROM H20 LEDGE, ATTACH #8 LOOP AT 4 SIDE OF POOL TO REBAR, THIS IS A DECK GROUNDING SYSTEM, #8 TO BE BELOW POOL DECK
2) NOTE: BRASS CONDUIT IS MAIN BOND TO EQUIP. FROM POOL GRID
3) HOME RUN FOR H20 OK, ELECTRIC NOT INSTALLED YET