Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA PRE-GUNITE
Permit Number - T08BU00118
Inspection Description - POOL/SPA PRE-GUNITE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/07/2008 | POOL/SPA PRE-GUNITE | Approved | ||
03/05/2008 | POOL/SPA PRE-GUNITE | Partial Approval | IVRS - Inspection :* 1) PLEASE INSTALL #8 CU. AROUND POOL PERIMETER 18"-24" AWAY FROM H20 LEDGE, ATTACH #8 LOOP AT 4 SIDE OF POOL TO REBAR, THIS IS A DECK GROUNDING SYSTEM, #8 TO BE BELOW POOL DECK 2) NOTE: BRASS CONDUIT IS MAIN BOND TO EQUIP. FROM POOL GRID 3) HOME RUN FOR H20 OK, ELECTRIC NOT INSTALLED YET |