Permit: T07PL02166

Parcel: 12112301A


Addresses:

5246 E LEE ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/20/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
10.2 PSI
COMPLETE B VENT AT WH
12/19/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
13.5 - 12 PSI
- SYSTEM IS LEAKING
- UNIONS CANNOT BE CONCEALED. L&R NIPP & COUPLING ALLOWED BELOW GRADE AT EXTERIOR
- TYPE B VENT REQUIRED AT FURNACE AND WATER HEATER
- AGA VALVES REQUIRED
- T&P SHALL TERMINATE 6"-24" ABV. GROUND
- ELECTRICAL BONDING
- EXISTING PIPING BELOW HOME CAN ONLY BE ACCEPTED IF TEST IS TIGHT