Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/20/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 10.2 PSI COMPLETE B VENT AT WH |
|
| 12/19/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 13.5 - 12 PSI - SYSTEM IS LEAKING - UNIONS CANNOT BE CONCEALED. L&R NIPP & COUPLING ALLOWED BELOW GRADE AT EXTERIOR - TYPE B VENT REQUIRED AT FURNACE AND WATER HEATER - AGA VALVES REQUIRED - T&P SHALL TERMINATE 6"-24" ABV. GROUND - ELECTRICAL BONDING - EXISTING PIPING BELOW HOME CAN ONLY BE ACCEPTED IF TEST IS TIGHT |