Permit: T07PL02152

Parcel: 13005310A


Addresses:

2116 E 34TH ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/26/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
12/19/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NO TEST ON SYSTEM, READ ALL NOTES & COMPLY
A REFEE COULD BE APPLIED TO THIS INSPECTION FOR FAILURE TO COMPLY
12/18/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
SHALL RETEST GAS PIPING SYSTEM AND HAVE 10PSI MINIMUM ON TEST GAUGE AT TIME OF REINSPECTION AS REQUEST
ON 12/17/07 INSPECTION SHEET.

SHALL PROVIDE BONDING OF BUILDING GAS PIPING AS REQUESTED ON 12/17/07 INSPECTION SHEET. FAILURE TO COMPLY CAN RESULT IN REINSPECTION FEES.
12/17/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. SHALL SUPPORT GAS PIPING AT METER AND DROP AT WATER HEATER/STOVE
2. VENT FROM WATER HEATER TO HAVE MINIMUM 1" CLEARANCE FROM ROOF (FLAMMABLE MATERIAL) AND TERMINATE MINIMUM 2' ABOVE TOP OF ROOF
3. PROVIDE BLOCKING UNDER GAS PIPING ON ROOF STRUCTURE AND SECURE PIPING TO BLOCKING.
4. PROVIDE BONDING OF BUILDING GAS PIPING
5. SHALL PROVIDE WEATHERPROOF ENCLOSURE FOR WATER HEATER.