Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
05/09/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. I BELIEVE THAT THE GAS LINE IS UNDERSIZED
WHEN WAS THE ROOFTOP UNIT INSTALLED?
PROVIDE INSPECTION HISTORY FOR UNIT
2. PROVIDE AN ACCURATE ISOMETRIC DRAWING, SHOWING DEVELOPED LENGTH AND TOTAL BTU CONSUMPTION APPROVED BY THE CITY
3. WATER HEATER VENT NOT APPROVED
4. NO SEDIMENT TRAPS AT GAS PACK OR WATER HEATER
5. NO T&P RELIEF DRAIN AT WATER HEATER
6. DRYER VENT MAY NOT DISCHARGE INTO ENCLOSURE
7. PROVIDE ACCESS TO ROOF
MAY NOT BE A COMPLETE LIST
WATER IS ALSO UNDERSIZED