Permit: T07PL02127

Parcel: 122091970


Addresses:

4102 E SENECA ST

Inspection Status: Not ready for Inspection

Inspection History: PLUMBING - GAS RECONNECT

Date Description Inspector Results Comments
12/14/2007 PLUMBING - GAS RECONNECT Not ready for Inspection IVRS - Inspection :*
1. ALL UNDERGROUND GAS PIPING IS TO BE INSTALLED AT LEAST 12" DEEP AT ALL POINTS. UNDERGROUND PIPING TO BE SCOTCHCOAT. PIPING RUN JUST BELOW GRADE, AT GRADE, IR JUST ABOVE GRADE NOT PERMITTED. PAINTING OF PIPE IS NOT CONSIDERED ADEQUATE PROTECTION
1211.1 2006 UPC PIPING UNDERGROUND
1211.3 2006 UPC PROTECTION AGAINST CORROSION

SEE INSTALLATION STANDARD 13 - INSTALLATION OF PROTECTIVELY COATED PIPE

2. PRESSURE TEST OK
3. WATER HEATER WILL REQUIRE PERMIT
INSTALL HEATER