Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/10/2007 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
| 12/06/2007 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* - 1/2 COURTESY CALL WAS GIVEN - HAVE ACCESS ARRANGED PRIOR TO INSPECTION - PIPING REQUIRES SUPPORT AT 8' O.C MAX AND AT CHANGES OF ELEVATION AND DIRECTION AND AT CONNECTION TO APPLIANCE. |
|
| 11/30/2007 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* - 12 PSI 11:21 - REPLACE MISSING OR DAMAGE PIPE SUPPORTS - SECURE PIPING - PIPING CANNOT BE UNDER STRAIN - PROVIDE A PERMIT AND PROOF OF INSPECTION ON UNIT - KEEP TEST ON PIPING |
|
| 11/28/2007 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* - PROVIDE AN AIR PRESSURE TEST WITH A 15 PSI GAUGE - PROVIDE ACCESS TO ROOFTOP FOR INSP. OF PIPING AND CONNECTION AT FURNACE. |