Permit: T07PL01999

Parcel: 11451142A

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T07PL01999

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/17/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
OK FOR GAS CALL SW GAS FOR SERVICE
12/11/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- IDENTIFY FURNACE FOR UNIT #345
- IDENTIFY GAS PIPING
- REPLACE DAMAGED AND MISSING PIPE SUPPORTS AT FURNACE CONNECTION
- PROVIDE AN AGA GAS VALVE
- SEAL WALL PENETRATION AT METER
12/03/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
PROVIDE ACCESS TO ROOF FOR INSP OF PIPING & FURNACE
ID PIPING W/MARKER
SEAL WALL PENETRATION
12 PSI ON 30 PSI GAUGE
11/27/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE PRESSURE TEST AT 10 PSI-ON 15 PSI GAUGE
2) IDENTIFY PIPING AT METER AND AT FURNACE LOCATION
3) PROVIDE ACCESS TO GAS APPLIANCES