Permit: T07PL01943

Parcel: 135112060

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T07PL01943

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
11/21/2007 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
11/20/2007 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. TEST TO BE AT MINIMUM 10 PSI AND HOLD WITH NO PRESSURE LOSS FOR 15 MINUTES
2. SYSTEM TO BE TESTED IN ITS ENTIRETY PIPING TEST TO APPLIANCE SHUT OFF VALVES THAT ARE AGA OR CSA APPROVED VALVES
3. ALL PIPING TO BE CORRECTLY SUPPORTED
4. WATER HEATER REQUIRES TEMPERATURE & PRESSURE RELIEF DRAIN PIPING GRAVITY DRAIN TO DAYLIGHT.
11/16/2007 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1. PRESSURE TEST NOT HOLDING
2. OWNER SAID, REPLACED UNION AT HOUSE ONLY PART WAY LEAKING