Permit: T07PL01893

Parcel: 127101010


Addresses:

6119 E 2ND ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
11/21/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
11/14/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
3/4" GAS PIPE 80' FROM METER IS NOT ADEQUATE TO SUPPLY A 100,000 BTU FURNACE & 34,000 BTU WATER HEATER
PROVIDE MIN. 1"