Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/28/2007 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* GAS CARD ON PIPE AT METER |
|
| 11/23/2007 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* 1. SHALL PROVIDE APPROVED COUPLINGS (NOT THREAD PROTECTORS) 2. ALL TOOL MARKS & FITTINGS UNDERGROUND TO BE PRIMED THEN TAPPED 3. SHALL PROVIDE AGA OR CSA APPROVED GAS SHUT OFF VALVE AT BUILING SERVICE ENTRY 4. WATER HEATER TO BE INSTALLED CORRECTLY AND SHALL HAVE UPPER COMBUSTION AIR TO EQUAL 100 SQ. INCHES 5. WATER HEATER TEMPERATURE & PRESSURE RELIEF SHALL GRAVITY DRAIN TO DAYLIGHT OR PROVIDE PETITION OF APPEAL FOR ALTERNATE FORM OF TEMPERATURE & PRESSURE RELIEF SIGNED BY CITY ON SITE WITH CORRECT INSTALLATION. 6. PROVIDE BONDING OF BUILDING GAS SYSTEM 7. PROVIDE SEDIMENT TRAP FOR WATER HEATER & FURNACE 125 PSI PRESSURE RELIEF DEVICE |
|
| 11/20/2007 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NO ONE HOME UNABLE TO INSPECT INSIDE HOME 2. PLEASE HAVE ADULT HOME FOR INSPECTION THANK YOU |
|
| 11/13/2007 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GAS TEST HAS 2 POUND 10 REQUIRED 2) PTR LINE SHALL DISCHARGE DOWNWARD INTO A PAN 6" FROM FLOOR |
|
| 11/06/2007 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* NO ONE AT HOME UNABLE TO DO INSPECTION |
|
| 11/02/2007 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* PLEASE MAKE ADDRESS VISIBLE EXPOSE REPAIR PROVIDE A 10 PSI PRESSURE TEST WITH A 15 PSI GAUGE PROVIDE ACCESS TO APPLIANCES |