Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T07PL01851

Parcel: 110071830

Inspection Status: Cancelled

Inspection History: ELECTRIC - FINAL

Permit Number - T07PL01851

Inspection Description - ELECTRIC - FINAL

Inspection Status - Cancelled

Date Description Inspector Results Comments
04/17/2008 ELECTRIC - FINAL Cancelled IVRS - RI canceled
04/17/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
OK ELECTRIC
04/15/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
EQUIPMENT GROUNDING CONDUCTOR TO BE GREEN ENTIRE LENGTH - 250.119
04/08/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. MAINTAIN WORKING CLEARANCES TO DISCONNECT
2. NEED LADDER
03/04/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PROPERLY SUPPORT CONDUIT DOWN WALL WITH APPROVED STRAPS & TIGHTEN LOOSE FITTINGS
2. USE APPROVED FITTINGS FOR WET LOCATION
3. A DISCONNECTING MEANS IS NEEDED
4. GROUND JUNCTION BOX ON HEATER
5. PLEASE PROVIDE ROOF ACCESS