Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T07PL01816

Parcel: 122162080


Addresses:

2031 N WINSTEL BL

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/19/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
08/18/2008 PLUMBING - FINAL Cancelled IVRS - RI canceled
04/21/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. YOU REQUIRE A PETITION OF APPEAL TO BE ON SITE AT TIME OF INSPECTION
-- REQUIRE A 90 DEG. TURN DOWN AT
PRESSURE RELIEF VALVE
-- NO THREADED END
-- REQUIRE AVB'S ON HOSE BIBBS
-- ATMOSPHERIC VACUUM BREAKERS

2. 3/4" CXMIP ADPT
3. 3/4" CXFTG ST 90 DEG.
01/18/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
- VENT TO BE APPROVED TYPE
- T&P RELIEF NOT APPROVED
- GAS VALVE NOT APPROVED
- NO BOND BETWEEN GAS AND WATER
- REQUIRE DIELECTRIC PROTECTION BETWEEN UPPER & GALVANIZED