Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/30/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* GAS CARD AT METER WEATHER SEAL YOUR ROOF FLASHINGS WHERE PIPE PENETRATES ROOF - SW GAS 889-1888 |
|
| 10/22/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SUPPORT GAS PIPING AT METER LOCATION 2. PROVIDE FLASHING FOR ALL PIPE PENETRATIONS THRU ROOF AND THEY SHALL BE WEATHER TIGHT 3. PROVIDE AGA OR CSA LISTED GAS APPLIANCE SHUT OFF VALVES AT APPLIANCES (3090) 4. SUPPORT GAS PIPING AT ROOFTOP UNIT 5. SUPPORT GAS PIPING AT WATER HEATER VALVE 6. WATER HEATER TEMPERATURE & PRESSURE RELIEF DRAIN TO BE RIDGID FULL SIZE PIPE GRAVITY DRAINING (NO FLEX) 7. PROVIDE SEDIMENT TRAP AT GAS ENTRY TO WATER HEATER & FURNACE RETEST & RECALL INSPECTION |