Permit: T07PL01742

Parcel: 112061630


Addresses:

2643 N TUCSON BL

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
11/07/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
CORRECTIONS MADE OK
OK FOR GAS
UCC LEFT AT METER
SW GAS 889-1888
10/22/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
REATLACH ELECTRIC BOND/GROUND
VENT FOR WATER HEATER TO EXTEND MINIMUM FIVE FEET ABOVE THE TOP OF THE HEATER
10/15/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- WATER PIPING BELOW GRADE IS NON-METALLIC BOND TO PANEL
- GAS YARD PIPING AND PRESSURE TEST OK
- WATER PIPE INSULATION IS ALREADY COMING OFF
- INSTALL PER MANUFACTURES INSTRUCTIONS
USE CONTACT CEMENT
- REMOVE SHARP BURRS FROM UNISTRUT
- FURN. VENT IS LEAVING SUPPORT ALSO, IT IS STILL UPSIDE DOWN
- PROVIDE LADDER TO ACCESS
- OK TO COVER INTERIOR WALLS
10/11/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- YARD WATER OK TO COVER
- REMOVE EXCESS FLUX FROM SOLDER JOINTS W/DAMP RAMP PER UPC
- INSULATE EXPOSED EXTERIOR PIPING
- SECURE TRACER WIRE
- VAC BREAKERS NOT REQUIRED ON WASHER BIBS
- REMOVE COOLER BLEED OFF FROM VENT MAY DRAIN TO YARD
- YARD GAS PIPING HAS TOOL MARKS AND A 90 THAT NEEDS TO BE WRAPPED
- ALSO, SUPPORT PIPING CONTINUOUSLY AND PIPING SHALL NOT BE UNDER STRAIN
- FURN VENT IS UPSIDE DOWN
- BOND GAS LINE